Carrier 25hba Installation Instructions Manual

Download Installation instructions manual of Carrier 25hba Heat Pump for Free or View it Online on All-Guides.com.

Brand: Carrier

Category: Heat Pump

Type: Installation instructions manual for Carrier 25hba

Pages: 8

Download Carrier 25hba Installation instructions manual

Carrier 25hba Installation instructions manual - Page 1
1
Carrier 25hba Installation instructions manual - Page 2
2
Carrier 25hba Installation instructions manual - Page 3
3
Carrier 25hba Installation instructions manual - Page 4
4
Carrier 25hba Installation instructions manual - Page 5
5
Carrier 25hba Installation instructions manual - Page 6
6
Carrier 25hba Installation instructions manual - Page 7
7
Carrier 25hba Installation instructions manual - Page 8
8
rn to the Expertg_
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol/_.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
ELECTRICAL SHOCK HAZARD
5,
6,
7.
g,
9.
10.
When passing refrigerant tubes through the wall. seal
opening with RTV or other pliable silicon-based caulk.
(See Fig. 1.)
Avoid direct tubing contact with water pipes, duct work.
floor joists, wall studs, floors, and walls.
Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing.(See Fig. 1.)
Ensure that tubing insulation is pliable and completely
surrounds vapor tube.
When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 1.)
Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
NOTE: Avoid contact between tubing and structure
7 OUTDOOR WALL'-_ INDOOR WAL_7
CAULK LIQUID TUBE
b........J .............r'q
THROUGH THE WALL
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb
vibration.
SUSPENSION
Fig. 1 - Connecting Tubing Installation
A94028
When outdoor unit is connected to factory-approved indoor unit.
outdoor unit contains system refrigerant charge for operation with
ARI rated indoor unit when connected by 15 ft. (4.57 m) of
field-supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of
this instruction.
IMPORTANT: Maximum liquid-line size is 3/8-in. OD for all
residential applications including line line.
IMPORTANT: Always install the factory-supplied liquid-line
filter drier. Obtain replacement filter driers from your distributor or
branch.