Juniper EX9214 Hardware Manual
Download Hardware manual of Juniper EX9214 Network Router, Switch for Free or View it Online on All-Guides.com.
Brand: Juniper
Category: Network Router , Switch
Type: Hardware manual for Juniper EX9214
Pages: 372
Before you begin connecting DC power to an EX9214 switch:
•
Ensure that you have taken the necessaryprecautions to preventElectrostatic discharge
(ESD) damage (see “Prevention of Electrostatic Discharge Damage” on page 329).
•
Ensure that you have connected the switch chassis to earth ground.
CAUTION: To meet safety and electromagnetic interference (EMI)
requirements and to ensure proper operation, you must connect EX9214
switches to earth ground before you connect them to power. For
installations that require a separate grounding conductor to the chassis,
use the protective earthing terminal on the switch chassis to connect to
earth ground. For instructions on connecting an EX9214 switch to ground
using a separate grounding conductor, see “Connecting Earth Ground to
an EX Series Switch” on page 147.
•
Install the power supply in the chassis. See “Installing a DC Power Supply in an EX9214
Switch” on page 193.
Ensure that you have the following parts and tools available to connect DC power to an
EX9214 switch:
•
ESD grounding strap
•
DC power source cables (not provided) with the cable lugs (provided) attached.
The provided cable lugs in an EX9214 switch are sized for 6 AWG (13.3 mm
2
) power
source cables.The DC power source cables that you provide must be 6 AWG (13.3 mm
2
),
minimum 60°C wire. We recommend that you install heat-shrink tubing insulation
around the power cables and lugs.
•
7/16 in. (11 mm) torque-controlled driver or socket wrench
•
Phillips (+) screwdriver, number 2
•
Multimeter
WARNING: Ensure that the power cords do not block access to switch
components or drape where people can trip on them.
To connect DC power to an EX9214 switch:
1. Switch off the dedicated customer site circuit breakers. Ensure that the voltage across
the DC power source cable leads is 0 V and that there is no chance that the cable
leads might become active during installation.
2. Attach the ESD grounding strap to your bare wrist, and connect the strap to the ESD
point on the chassis.
159Copyright © 2017, Juniper Networks, Inc.
Chapter 12: Connecting the Switch to Power