Table 61: Parts and Tools Required for Connecting an EX Series Switch to Earth
Ground (continued)
Additional
InformationScrewdriver
Screws and
Washers
Grounding Lug
Specifications
Grounding Cable
Requirements
Earthing
Terminal
LocationSwitch
Phillips (+)
number 2
•
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer
—provided
•
Two #¼” flat
washers—
provided
Panduit
LCD2-14A-Q or
equivalent
—provided
6 AWG (13.3
mm²), minimum
60°C wire, or as
permitted by the
local code
Left side of
the chassis
EX8208
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 151.
Phillips (+)
number 2
•
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer
—provided
•
Two #¼” flat
washers—
provided
Panduit
LCD2-14A-Q or
equivalent
—provided
2 AWG (33.6
mm²), minimum
60°C wire, or as
permitted by the
local code
Two
earthing
terminals:
•
Left side
of the
chassis
•
Rear
panel of
the
chassis
EX8216
See
“Grounding
Cable and
Lug
Specifications
for EX9200
Switches” on
page 100.
Phillips (+)
number 2
•
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer—
provided
•
Two #¼” flat
washers—
provided
Thomas&Betts
LCN6-14 or
equivalent—
provided
One 6 AWG (13.3
mm²), minimum
60°C wire, or one
thatcomplieswith
the local code
Rear panel
of the
chassis
EX9204
See
“Grounding
Cable and
Lug
Specifications
for EX9200
Switches” on
page 100.
Phillips (+)
number 2
•
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer—
provided
•
Two #¼” flat
washers—
provided
Thomas&Betts
LCN6-14 or
equivalent—
provided
One 6 AWG (13.3
mm²), minimum
60°C wire, or one
thatcomplieswith
the local code
Rear panel
of the
chassis
EX9208
See
“Grounding
Cable and
Lug
Specifications
for EX9200
Switches” on
page 100.
Phillips (+)
number 2
•
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer—
provided
•
Two #¼” flat
washers—
provided
Thomas&Betts
LCN6-14 or
equivalent—
provided
One 6 AWG (13.3
mm²), minimum
60°C wire, or one
thatcomplieswith
the local code
Rear panel
of the
chassis
EX9214
Copyright © 2017, Juniper Networks, Inc.150