1: OPERATING AREA AND CONDITIONS
The Bacharach MGS Series controllers provide local
alarm status indicaons (via mul-colored, per-
channel LEDs) as well as common single-level or
dual-level digital (relay) alarm outputs based on 1, 2,
4, or 6 input signals and 1 or 2 user-definable
set-points.
MGS Controllers support mulple input sensors/
transmiers (1, 2, 4, or 6 channels) based on the
model of the controller. Inputs are standard 4-20 mA
signals from MGS-series sensors or any standard,
linear, 4-20 mA transmier.
The instrument is powered 100V-230V AC (50-60Hz) or
12V DC (specified at me of order).
P/N: 6709-9002
Revision 0
January 25, 2016
2: SAFETY INSTRUCTIONS
USER MANUAL: Before using this equipment,
carefully read and strictly follow the User
Manual (part number 6709-9000). The user
must fully understand and strictly observe the
instrucons. Use the equipment only for the
purposes listed and under the condions speci-
fied in those documents.
CODE COMPLIANCE: Comply with all local and
naonal laws, rules and regulaons associated
with this equipment.
GENUINE PARTS: Use only genuine Bacharach
spare parts and accessories, otherwise proper
funconing of the equipment may be impaired.
TECHNICIAN USE ONLY: This unit must be
installed by a suitably qualified technician who
will install this unit in accordance with these
instrucons and the standards in their parcular
industry/country. Operators of the unit should
be aware of the regulaons and standards in
their industry/country for the operaon of this
unit. These notes are only intended as a guide
and the manufacturer bears no responsibility for
the installaon or operaon of this unit.
Failure to install and operate the unit in accor-
dance with these instrucons and with industry
guidelines may cause serious injury including
death and the manufacturer will not be held
responsible in this regard.
SAFE MOUNTING: This controller must be
connected by a marked, suitably located and
easily reached switch or circuit-breaker as
means of disconnecon.
WARNING: Strictly follow the instruc-
ons in the Controller Manual (part
number 6709-9000) available at
www.MyBacharach.com.
CAUTION: DO NOT MOUNT the MGS
Controller in an area that may contain
flammable liquids or vapors. Opera-
on of electrical equipment in such
an area constutes a safety hazard.
World Headquarters
621 Hunt Valley Circle
New Kensington, PA 15068 USA
Phone: 724-334-5000 • Fax: 724-334-5001
Toll Free: 1-800-736-4666
Website: www.MyBacharach.com
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388 • Fax: +353 1 284 6389
INSTALLATION GUIDE
4: DIMENSIONS
ENVIRONMENTAL CONSIDERATIONS: Care-
fully consider the full range of environmental
condions to which the instruments will be
exposed.
APPLICATION CONSIDERATIONS: The specifics
of the applicaon (for example, possible leaks,
air movement/dra, etc.) must be observed.
ACCESSIBILITY CONSIDERATIONS: The degree
of accessibility required for maintenance
purposes must be granted.
ACCESSORY CONSIDERATIONS: The types of
oponal and accessory equipment that will be
used with the system must be kept in mind.
ELECTRONIC CONSIDERATIONS: The system
contains sensive electronic components that
can be easily damaged. Do not touch nor
disturb any of these components.
Mount the MGS Controller according to the
above consideraons, product dimensions (see
Secon 4), and the maximum wiring lengths
(see Secon 5).
3: MOUNTING
Controller Housing
(1-2 Channels)
0.6 in
(15.5 mm)
0.6 in (15.0 mm)
0.5 in (12.7 mm)
2.9 in (74.5 mm)
0.2 in
(4.8 mm)
0.2 in
(5.0 mm)
2.0 in
(50.0 mm)
0.4 in (10.0 mm)
Screw
Screw
0.4 in (9.0 mm)
0.5 in (12.7 mm)
0.6 in
(15.0 mm)
1-2 Sensor
Controller
Housing
O 0.18 in (4.60 mm)
O 0.20 in (5.10 mm)
Mounng
Hole
9.47 in (240.50 mm)
8.85 in (224.70 mm)
10.26 in (260.50mm)
5.13 in (130.25 mm)
9.55 in (242.50 mm)
4-6 Sensor
Controller Housing
Controller Housing
(4-6 Channels)
5: WIRING
1: Strip 0.2 to 0.25 inches (5 to 7 mm)
of wiring insulaon.
2: Connect the wires as indicated.
SHIELD WIRE WARNING: Connect the
shield of the power wires to the earth
ground of the central control system
(e.g., chassis, ground bus bar, etc.).
WARNING: The mains power supply
cable should be of an approved type
based on local regulaons. Connecon
to the mains power supply must be
made via an approved, readily-
accessible, switched and fused plug and
socket (or as per local wiring regula-
ons) which should be within 19 feet (3
meters) of the sesnor/transmier.
CABLE OPENINGS: The metal controller housing
provides a number of PG7 openings for cable glands
or plugs.
NOTE: Aer wiring is completed,
carefully re-assemble the enclosure and
its components.
Refer to the User Manual (part number 6709-
9000) at www.MyBacharach.com for detailed
instrucons on accessing the internal components
for wiring.
Refer to the Controller manual (part
number 6709-9000) at
www.MyBacharach.com for addional
wiring configuraons.