Guide Specification
Item #: 409955
Rev Date: 2015-05-12
fantech
SHR 6904 • 8004 • 11004 • 14104
Commercial Heat Recovery Ventilators Ducted Indoor Models
Part I – Genral
Product Specification
Heat Recovery Ventilator shall be as manufactured by “Fantech” or approved equal provided all specifications are met. Fantech SHR commercial
series shall be used as the basis of design.
Requirements
Unit shall be CSA Certified to safety standards CSA C22.2 No. 113 Fans and Ventilators and UL 1812 Ducted Heat Recovery Ventilators.
Performance shall be as scheduled on plans.
Exhaust discharge and outside air intake shall be located on the same side.
The unit shall be capable of operating in winter and summer conditions without any loss of ventilation capacity.
The Heat recovery core shall be of aluminum fixed plate, cross flow construction, with no moving parts.
Part II – Product
Cabinet
Cabinet shall be constructed of G90 galvanized, 20 gauge steel sheet with lapped corners. All exposed surfaces shall be coated with baked
powder paint. All seams shall be sealed, requiring no caulking at job site.
The unit shall be fitted with a full length drain pan for controlled condensate drainage including two drains spouts with ½ inch (12.7 mm) barbed
fittings for easy connection.
Unit casing shall be insulated with 1 inch (25 mm) fiberglass with FSK facing. SHR8004 and SHR14104 are insulated with 2 inch (50 mm) of
foil-faced high density polystyrene foam on the outdoor air side for condensation control. The flame spread index of the insulation material shall
not be over 25 and its smoke developed index shall not be over 50 when tested in accordance with the Standard for Tests for Surface Burning
Characteristics of Building Material, UL723. Insulation shall be secured to unit with waterproof adhesive and permanent mechanical fasteners.
Heat Recovery Core
The heat recovery Core shall be a fixed plate cross-flow heat exchanger using 1100 alloy aluminum and capable of transferring sensible heat
between air streams. The heat recovery core shall be engineered with a turbulence inducing geometry in order to maximize heat transfer while
allowing an effective evacuation of condensate. The plates shall be hemmed to avoid cross-contamination of airstreams. The flame spread index
of the heat recovery core shall not be over 25 and its smoke development index shall not be over 50 when tested in accordance with the Standard
for Tests for Surface Burning Characteristics of Building Material, UL723.
Frost Control
A preset frost control sequence is initiated if the outdoor air temperature falls below the set point of 23°F (-5°C). During the initial stage, the
supply blower shuts down & the exhaust blower switches into high speed to eliminate frost build-up in the core. The unit then returns to normal
operation for the final stage of the frost control sequence at which time the sequence is repeated if the outdoor air temperatures is still below
the set point.
Electrical
Electrical box shall be isolated from the airflows and all integral wires and connections protected.
All internal electrical components shall be factory wired for single point power connection.
All electrical components shall be UL Listed or Recognized and CSA Certified or Accepted where applicable and wired in compliance with the
National Electrical Code.