LG K3P-07AS Datasheet

Download Datasheet of LG K3P-07AS Controller for Free or View it Online on All-Guides.com. This version of LG K3P-07AS Manual compatible with such list of devices, as: K3P-07AS, K3P-07BS, K3P-07CS, MASTER-K200S

Brand: LG

Category: Controller

Type: Datasheet

Model: LG K3P-07AS , LG K3P-07BS , LG K3P-07CS , LG MASTER-K200S

Pages: 2

Download LG K3P-07AS Datasheet

LG K3P-07AS Datasheet - Page 1
1
LG K3P-07AS Datasheet - Page 2
2
LG Programmable Logic Controller
MASTER-K200S
CPU Module
K3P-07AS
K3P-07BS
K3P-07CS
Beijing Branch
Bangkok Branch
LG Industrial Systems LG Industrial Systems (Thailand)
Elevator Co., Ltd. Co., Ltd
T : +86-10-6462-3256 T : +66-2-381-8443
F : +86-10-6462-3255 F : +66-2-381-8445
Bogota Branch
Chicago Branch
LG Industrial Systems de LG Industrial Systems Co., Ltd.
Colombia S.A. Chicago Office
T : +57-1-310-6077 T : +1-708-692-4500
F : +57-1-310-5831 F : +1-708-692-4501
Dalian Branch
Hanoi Branch
Dalian LG Industrial Systems LG Industrial Systems Co., Ltd.
Co., Ltd. Hanoi Office
T : +86-411-281-2579 T : +64-4-821-0388
F : +86-411-281-2578 F : +64-4-821-0399
Hong Kong Branch
Shanghai Branch
LG Industrial Systems (HK) Ltd. Shanghai LG Industrial Systems Co., Ltd.
T : +852-2598-6615 T : +86-21-6248-2710
F : +852-2598-7105 F : +86-216248-3236
Singapore Branch
Taipei Branch
LG Industrial Systems Co., Ltd. LG Industrial Systems (Taiwan) Co. Ltd.
T : +65-323-7361 T : +886-2-516-5010
F : +65-323-7362 F : +886-2-516-5035
Tokyo Branch
LG Industrial Systems Co., Ltd. Tokyo Office
T : +81-3-3589-6362
F : +81-3-3588-1810
LG Industrial Systems Co., Ltd.
Head Office
LG Mullae Building 9
th
F, 10, Mullae-dong 6-ga, Yongdungpo-gu, Seoul, KOREA
Tel : +82-2-2006-3751~6 Fax : +82-2-2006-3951
Home page : http:www.lgis.lg.co.kr/fa
702006186
Before handling the product
Read this data sheet carefully prior to any operation, mounting, installation or
start-up of the product.
Materials for MASTER-K
Name Code
MASTER-K KGL-WIN (Programming software) 702005036
MASTER-K (Instructions & Programming) 702006539
MASTER-K CPU User’s Manual 702006391
Safety Precautions
Be sure to read carefully the safety precautions given in data sheet and user’s manual before
operating the module and follow them.
The precautions explained here only apply to the MASTER-K 200S CPU module. For safety
precautions on the PLC system, see the MASTER-K CPU User’s manual.
A precaution is given with a hazard alert triangular symbol to call your attention, and
precautions are represented as follows according to the degree of hazard..
!
!
However, a precaution followed with ‘Caution’ can also result in serious conditions.
Both of two symbols indicate that an important content is mentioned, therefore, be sure
to observe it. Keep this manual handy for your quick reference in necessary.
Design Precautions
Installation Precautions
Wiring Precautions
Make sure that FG the terminal is grounded with class 3 grounding which is
dedicated to the PLC. Otherwise, it can cause disorder or malfunction of PLC.
Before the PLC wiring, be sure to check the rated voltage and terminal
arrangement for the module and observe them correctly. If a different power, not of
the rated voltage, is applied or wrong wiring is provided, it can cause a fire or
disorder of the module.
Drive the terminal screws firmly to the defined torque. If loosely driven, it can cause
short circuit, a fire or malfunction.
Be careful that any foreign matter like wire scraps should not enter into the module.
It can cause a fire, disorder or malfunction.
Test RUN and maintenance precautions
Waste Disposal Precaution
This data sheet provides brief information about characteristics, configuration, and usage of
MASTER-K200S CPU modules (K3P-07AS, K3P-07BS, K3P-07CS).
No Item Specifications Standard
1
Operating
temperature
0 ~ 55
2
Storage
temperature
-25 ~ 70
3
Operating
Humidity
5 ~ 95%RH, non-condensing
4
Storage
humidity
5 ~ 95%RH, non-condensing
Occasional vibration
Frequency Acceleration Amplitude
Sweep
count
10
f
57 Hz
- 0.075 mm
57
f
150 Hz 9.8
{1G}
-
Continuos vibration
Frequency Acceleration Amplitude
10
f
57 Hz
- 0.035 mm
5 Vibration
57
f
150 Hz 4.9
{0.5G}
-
10 times
in each
direction
for
X, Y, Z
IEC 1131-2
6 Shocks
*Maximum shock acceleration: 147
{15G}
*Duration time :11 ms
*Pulse wave: half sine wave pulse
( 3 times in each of X, Y and Z directions )
IEC 1131-2
Square wave
impulse noise
±
1,500 V
Electrostatic
discharge
Voltage :4kV(contact discharge)
IEC 1131-2
IEC 801-2
Radiated
electromagnetic field
27 ~ 500 MHz, 10 V/m
IEC 1131-2
IEC 801-3
Severity
Level
All power
modules
Digital
I/Os
( Ue
24 V)
Digital I/Os
(Ue
<
24 V)
Analog I/Os
communication
I/Os
7
Noise
immunity
Fast transient burst
noise
Voltage 2 kV 1 kV 0.25 kV
IEC 1131-2
IEC 801-4
8 Atmosphere Free from corrosive gases and excessive dust
9
Altitude for
use
Up to 2,000m
10
Pollution
degree
2 or lower
11
Cooling
method
Self-cooling
Specifications
Items
K3P-07AS, K3P-07BS, K3P-07CS
Remark
Operation method
Cyclic operation of stored program
Time driven operation, Interrupt operation
I/O control method
Scan synchronized batch processing
method (Refresh method)
Programming Language
Ladder Diagram (LD)
Instruction List (IL)
Basic
instructions
30
Numbers
of
instructions
Application
instructions
218
Execution Time
0.5
/step
Program memory capacity 7k steps
Max. I/O points 256 points
P(I/O Relay) P000 ~ P15F (256 points)
M(Auxiliary Relay) M0000 ~ M191F (3,072 points)
K(Keep Relay) K000 ~ K31F (512 points)
L(Link Relay) L000 ~ L63F (1,024 points)
F(Special Relay) F000 ~ F63F (1,024 points)
T(Timer) T000 ~ T255 (256 points)
C(Counter) C000 ~ C255 (256 points)
S(Step Controller) S00.00 ~ S99.99 (100 x 100 steps)
Memory
Device
D(Data Register) D0000 ~ D4999 (5000 words)
Timer (5 type)
On Delay, Off Delay, Integrating, Monos-
table ,Retriggerable
Counter (6 type) Up, Down, Up-Down, Ring
Operation mode RUN,STOP,PAUSE,DEBUG
Self-diagnostic functions
Memory error detection, I/O error detection,
Operation delay monitoring etc.
Internal current consumption 0.17A
Weight (
)
0.11
1) Cyclic operation
A PLC program is sequentially executed from the first step to the last step, which is called scan. This
sequential processing is called cyclic operation. Cyclic operation of the PLC continues as long as
conditions do not change for interrupt processing during program execution.
Stages Processing
Operation Start
·
Stage for the start of a scan processing. It is executed only
Initialization one time when the power is applied or reset is executed. It
executes the following process.
I/O module reset
Self diagnosis
Data clear
I/O module address allocation
·
Read input module conditions and store it into the input image
Input image area refresh area before operation processing of a program.
Program operation
·
Program is sequentially executed from the first step to the last
The start of program step.
The end of program
·
The contents stored in the output image area is output to output
Output image area refresh modules when operation processing of a program is finished
·
Stage for return processing after the CPU module has finished
END processing 1 scan. The following processing are executed..
Self-diagnosis
Change of the present values of timer and counter, etc.
Check the status of mode setting switch
2) Time driven interrupt operation method
In time driven interrupt operation method, operations are processed not repeatedly but at every preset
interval. In the K200S CPU module, interval can be set to between 0.01 ~ 600 second. This operation is
used to process operation with a constant cycle
3) Event driven interrupt operation method
If a situation occurs which is requested to be urgently processed during execution of a PLC program,
this operation method processes immediately the operation which corresponds to interrupt program. The
signal which informs those urgent conditions to the CPU module is called interrupt signal. The K200S
CPU module has two kind of interrupt operation methods, which are internal and external interrupt signal
methods.
If not provided with proper prevention, it can cause death, fatal
injury or considerable loss of property
If not properly observed, it can cause a hazard situation to resul
t
in severe or slight injury or a loss of property.
Don not run I/O signal lines near to high voltage line or power line.
Separate them as 100mm or more as possible. Otherwise, noise can cause module
malfunction.
Operate the PLC in the environment conditions given in the general specifications..
If operated in other environment not specified in the general specifications, it can
cause an electric shock, a fire, malfunction or damage or degradation of the module.
Make sure the module fixing projections is inserted into the module fixing hole and
fixed.
Improper installation of the module can cause malfunction, disorder or falling.
Do not separate the module from the printed circuit board, or do not remodel the
module. They can cause disorder, malfunction, damage of the module or a fire. When
mounting or dismounting the module, perform them after the power has been turned off.
Do not change battery while power is off. It can cause loss of data.
Do not contact the terminals while the power is applied. It can cause malfunction.
When cleaning or driving a terminal screw, perform them after the power has been
turned off.
When disposing the module, do it as an industrial waste.
Caution
Caution
Caution
Warning
Caution
DATA SHEET
1
.
I
ntro
d
uct
i
on
2
.
G
enera
l
S
pec
ifi
ca
ti
ons
Warning
Caution
3
.
P
er
f
ormance
S
pec
ifi
ca
ti
ons
4
.
O
pera
ti
on
P
rocess
i
ng
M
e
th
o
d
PLC Others
< Best >
PLC Others PLC Others
< Good > < Bad >
Caution
LG Industrial Systems