Room Sensor Transceiver (RSX)
Item Number 563-067, Rev. BA Page 1 of 5
Figure 1. Room Sensor Transceiver.
Product Description
The Room Sensor Transceiver (RSX) allows
wireless communication between the Terminal
Equipment Controller (TEC) and Wireless Room
Sensor (WRS). The RSX is mounted at or near the
TEC and is powered by 24 Vac. The RSX is
connected to the TEC using the RSX/TEC
connection cable. The antenna can be mounted
directly to the radio or mounted remotely for
installations where the location of the RSX causes
the antenna to be shielded—for example, when the
RSX is mounted inside a TEC enclosure.
Product Numbers
563-069 Room Sensor Transceiver (RSX)
563-007 Direct Mount Antenna
563-008 Remote Mount Antenna
Transceivers do not come with antennas.
Antennas must be ordered separately.
Accessories
563-210-01 RSX/TEC Connection Cable (3 ft)
563-210-02 RSX/TEC Connection Cable (12 ft)
563-207 Auto-binding cable (to bind
WRS/RSX pair)
Warning/Caution Notations
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow the procedures as
specified.
Expected Installation Time
10 minutes
Required Tools and Materials
Electro-static discharge wrist strap
Small flat-blade screwdriver
Cordless drill/driver set
Prerequisites
All wiring must conform to NEC and local
codes and regulations.
24 Vac Class II power source is available
with enough power to support RSX (RSX
draws 1.2 VA).
Metal Oxide Varistors (MOVs) must be used
for TECs that switch high voltage devices.
For details, see the FSN for Terminal
Equipment Controllers (TECs) Failing when
Switching High Voltage Powered Devices.
Any application-specific hardware or device