1
Daikin 668811201 Installation, operation & application manual - Page 2
2
1.Turnoffpowertotheheatingandcoolingsystembyremovingthefuseorswitchingtheappropriate
circuitbreakeroff.
2.Removecoverofoldthermostat.Thisshouldexposethewires.
3.Labeltheexistingwireswiththeenclosedwirelabelsbeforeremovingwires.
4.Afterlabelingwires,removewiresfromwireterminals.
5.Removeexistingthermostatbasefromwall.
6.Refertothefollowingsectionforinstructionsonhowtoinstallthisthermostat.
To Remove Existing Thermostat
WARNING
ELECTRICAL SHOCK HAZARD – Turn off power at the main service panel by removing the fuse or
switching the appropriate circuit breaker to the OFF position before removing the existing thermostat.
Important Safety Information
• Thisthermostatisfor24VACapplicationsonly;donotuseonvoltagesover30VAC
• Donotshortacrossterminalsofgasvalveorsystemcontroltotestoperation;thiswilldamageyour
thermostatandvoidyourwarranty
• Allwiringmustconformtolocalandnationalelectricalandbuildingcodes
• Donotuseairconditioningwhentheoutdoortemperatureisbelow50degrees;thiscandamage
yourA/Csystemandcausepersonalinjuries
• Usethisthermostatonlyasdescribedinthismanual
WARNING
Always turn off power at the main power supply before installing, cleaning, or removing thermostat.
Congurationswitch
Resetswitch
Left(system)
button
Right(fan)
button
Downbutton
Upbutton
Fieldprogrammingpins
RC/RHJumper
Fanswitch
Parts Diagram
Icon Descriptions
Fanoperationicon
Coolingoperationicon
Heatingoperationicon
Specifications
Electrical rating: • 24VAC(18-30VAC)
• 1ampmaximumperterminal
• 3ampmaximumtotalload
Temperature control range: 45°Fto90°F(7°Cto32°C)Accuracy:±1°F(±0.5°C)
System congurations:1-stageheat,1-stagecool,heatpump,gas,oil,electric
Timing:
Anti-shortCycle:
4minutes
BacklightOperation
Terminations:S1,S2,Y,W/O/B,G2,G1,RC,RH,C
Package Contents/Tools Required
Package includes: Daikin 668811101 programmable thermostat and Operation and Application
Guide.
Wiring Diagrams
Hardwired
5-Wire, Single Transformer
WARNING
Be sure exposed portion of wires does not touch other wires.
To Install Thermostat
WARNING
ELECTRICAL SHOCK HAZARD – Turn off power at the main service panel by removing the fuse or
switching the appropriate circuit breaker to the OFF position before removing the existing thermostat.
IMPORTANT: Thermostat installation must conform to local and national building and electrical
codes and ordinances.
Note:Mount the thermostat about ve feet above the oor. Do not mount the thermostat on an
outside wall, in direct sunlight, behind a door, or in an area affected by a vent or duct.
1. Turnoffpowertotheheatingandcoolingsystembyremovingthefuseorswitchingthe
appropriatecircuitbreakeroff.
2. Toremovecover,pullgentlyattheseamatthetop.
3. Putthermostatbaseagainstthewallwhereyouplantomountit(Besurewireswillfeedthrough
thewireopeninginthebaseofthethermostat).
4. Marktheplacementofthemountingholes.
5. Setthermostatbaseandcoverawayfromworkingarea.
6. Usinga3/16”drillbit,drillholesintheplacesyouhavemarkedformounting.
7. Useahammertotapsuppliedanchorsinmountingholes.
8. Alignthermostatbasewithmountingholesandfeedthecontrolwiresthroughslitinthermal
intrusionbarrierandintowireopening.
9. Usesuppliedscrewstomountthermostatbasetowall.
10.For2transformersystems,removeanddiscardRC/RHjumper.
11.Insertstripped,labeledwiresinmatchingwireterminals.
12.Gentlytugwiretobesureofproperconnection.Doublecheckthateachwireisconnectedtothe
properterminal.
13.Turnonpowertothesystematthemainservicepanel.
14.Congurethermostattomatchthetypeofsystemyouhave.
15.Replacecoveronthermostatbysnappingitinplace.
16.Testthermostatoperationasdescribedin“TestingtheThermostat”.
Configuration Mode
OFF
1. VerifythethermostatisintheOFFmode.
PresstheSYS(left)buttonuntiloffmodedisplays.
2. Removethecoverofthethermostatbygentlypullingnearoneofthe
cornersatthetopofthethermostat.
Presstheupordownbuttontochangesettingswithineachscreen.
Down
button
Up
button
Toexitcongurationmode,presstheCONFIGswitchfor1second.
Presstherightbuttontoadvancetothenextscreen.
Note:Pressing the
left
button will return you to the previous screen.
Left
button
Right
button
ThecongurationmodeisusedtosettheDaikinthermostattomatchyourheating/coolingsystem.
Thisthermostatfunctionswithheatpump,airconditioning,gas,oilorelectricheatsystems.
Tocongurethethermostat,performthefollowingsteps:
3. PresstheCONFIGbuttonfor1secondwhilethethermostatisinOFF
mode.
S1 S2 Y W
O/B
G RC RH C
RESET CONFIG
RC
RH
FP
CONFIG
Hardwired
5 or 6-Wire, Single Transformer
Hardwired
5-Wire, Single Transformer
Configuration Mode Settings
2.Temperature Differential (1°Fto5°F)(0.5°Cto2.5°C)
Setthenumberofdegreesbetweenyour“setpoint”temperatureandyour
“turnon”temperature.
Presstheupordownbuttontosetdifferentialvalue.
Presstheright buttontoadvancetothenextscreen.
ThesetupscreensforCongurationModeareasfollows:
1.Temperature Scale (ForC)
ChooseFahrenheitorCelsius.
Presstheupordownbuttontoselect.
Pressthe
right
buttontoadvancetothenextscreen.
3.Deadband (1°F-9°F)(1°C-5°C)
Settheminimumnumberofdegreesbetweenyourheatsetpointandyour
coolsetpointinAutochangeovermode.
Presstheupordownbuttontosetdeadbandvalue.
Presstherightbuttontoadvancetothenextscreen.
Choose System
Reversing Valve
Active
Number of Compressors
or Compressor Stages
Type of
Heat
Heat Pump
HP O 1
HP b 1
Non-Heat
Pump
Heat Gas
Heat Electric
Presstheupordownbuttontoselect.
Presstherightbuttontoadvancetothenextscreen.
4. System –Setforheatpump,non-heatpump,reversingvalveoperationandnumberof
compressorsinyoursystem.
5. Lockout (0-8°,COOL-HEAT)
Selectthenumberofdegreessettemperaturecanbechangedduring
keypadlockout.COOL-HEATlockoutallowsadjustmentoftheset
temperaturestothemaximumheatsettemperatureselectedinStep6and
minimumcoolsettemperatureselectedinStep7.
Note:The mode cannot be changed when the thermostat is locked.
Presstheupordownbuttontoselect.
Presstherightbuttontoadvancetothenextscreen.
6. Maximum Heat Setpoint(45°Fto90°F)(7°Cto32°C)
Adjusttocontrolthemaximumheatsettemperatureallowed.
Presstheupordownbuttontoselect.
Presstherightbuttontoadvancetothenextscreen.
Daikin P/N (668811201)
Installation, Operation & Application Guide
Version B: 10-15-13
Non-Programmable Electronic Thermostat
• Configurable
• Single-Stage Heat/Cool Systems
• Single-Stage Heat Pump Systems
• Two Speed Fan Control
• Large Display With Backlight
• Selectable Fahrenheit or Celsius
• Compatible with Gas, Oil, or Electric
• SimpleSet™ Field Programming
• Status Indicator Light
• Relay Outputs (minimum voltage drop in thermostat)
• Remote Sensor Compatible
• Ideally Suited for:
– Residential (New Construction/Replacement)
– Light Commercial
1 Heat/1 Cool, Auto Changeover, Fan Speed Control, Hardwire
Remote or Outdoor Sensor Installation (Optional)
1. Removecoverfromremotesensorhousing.RequiredDaikin
RemoteSensorPartNo.667720401
2. Selectanappropriatelocationformountingtheremote
sensor.
3. Mountremotesensorunitusinghardwareprovided.
4. Installtwostrandshieldedwirebetweenremotesensorand
thermostat.Shieldedwiremustbeused.Do notrunremote
sensorwireinconduitwithotherwires.
• Wire 1shouldrunbetweentheS1terminalonthe
thermostatandtheS1terminalontheremotesensor
• Wire 2shouldrunbetweentheS2terminalonthethermostatandtheS2terminalontheremotesensor
• ConnecttheshieldingofthewiretotheS2terminalonthethermostat
5. Congurethethermostattooperatewiththeremotesensor(seeCongurationModesetting10).
Note:Remote or outdoor sensor reading can be displayed by simultaneously pressing the
Down and SYS buttons.
Remote Sensor