FORM 201.19-EG4
Dimensions – YCAS0308EB (English)
LD06121
21 1/4"
91 13/16"
88"
1 7/8"
B
C
C
B
42"
31 1/2"
2"
7"
7 1/2"
(12) 1/2"
12"
28"
2" TYP.
9"
2"
4 3/4"
4 5/16" (EDGE OF
CONNECTION)
BASE TO COOLER
VIEW A-A
OPTIONS PANEL
CONTROL CENTER
MICROCOMPUTER
OPENING
(9" HIGH)
OPENING
(21" HIGH)
CONTROL
POWER
VIEW C-C
CONTROL ENTRY
CONDUIT K.O.'S
VIEW B-B
TRANSFORMER
CONTROL
SERVICE SWITCH
POWER: MULTIPLE POINT WITH TERMINAL BLOCKS
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reli-
able operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
air ow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety
cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit
is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 6'; rear to wall - 6'; control panel end to wall - 4'; top
- no obstructions allowed; distance between adjacent units - 10'. No more than one adjacent wall may be higher than the unit.