York R-407C Optimized Manual

Download Manual  of York R-407C Optimized Chiller for Free or View it Online on All-Guides.com.

Brand: York

Category: Chiller

Type: Manual  for York R-407C Optimized

Pages: 120

Download York R-407C Optimized Manual 

York R-407C Optimized Manual  - Page 1
1
York R-407C Optimized Manual  - Page 2
2
York R-407C Optimized Manual  - Page 3
3
York R-407C Optimized Manual  - Page 4
4
York R-407C Optimized Manual  - Page 5
5
York R-407C Optimized Manual  - Page 6
6
York R-407C Optimized Manual  - Page 7
7
York R-407C Optimized Manual  - Page 8
8
York R-407C Optimized Manual  - Page 9
9
York R-407C Optimized Manual  - Page 10
10
York R-407C Optimized Manual  - Page 11
11
York R-407C Optimized Manual  - Page 12
12
York R-407C Optimized Manual  - Page 13
13
York R-407C Optimized Manual  - Page 14
14
York R-407C Optimized Manual  - Page 15
15
York R-407C Optimized Manual  - Page 16
16
York R-407C Optimized Manual  - Page 17
17
York R-407C Optimized Manual  - Page 18
18
York R-407C Optimized Manual  - Page 19
19
York R-407C Optimized Manual  - Page 20
20
York R-407C Optimized Manual  - Page 21
21
York R-407C Optimized Manual  - Page 22
22
York R-407C Optimized Manual  - Page 23
23
York R-407C Optimized Manual  - Page 24
24
York R-407C Optimized Manual  - Page 25
25
York R-407C Optimized Manual  - Page 26
26
York R-407C Optimized Manual  - Page 27
27
York R-407C Optimized Manual  - Page 28
28
York R-407C Optimized Manual  - Page 29
29
York R-407C Optimized Manual  - Page 30
30
York R-407C Optimized Manual  - Page 31
31
York R-407C Optimized Manual  - Page 32
32
York R-407C Optimized Manual  - Page 33
33
York R-407C Optimized Manual  - Page 34
34
York R-407C Optimized Manual  - Page 35
35
York R-407C Optimized Manual  - Page 36
36
York R-407C Optimized Manual  - Page 37
37
York R-407C Optimized Manual  - Page 38
38
York R-407C Optimized Manual  - Page 39
39
York R-407C Optimized Manual  - Page 40
40
York R-407C Optimized Manual  - Page 41
41
York R-407C Optimized Manual  - Page 42
42
York R-407C Optimized Manual  - Page 43
43
York R-407C Optimized Manual  - Page 44
44
York R-407C Optimized Manual  - Page 45
45
York R-407C Optimized Manual  - Page 46
46
York R-407C Optimized Manual  - Page 47
47
York R-407C Optimized Manual  - Page 48
48
York R-407C Optimized Manual  - Page 49
49
York R-407C Optimized Manual  - Page 50
50
York R-407C Optimized Manual  - Page 51
51
York R-407C Optimized Manual  - Page 52
52
York R-407C Optimized Manual  - Page 53
53
York R-407C Optimized Manual  - Page 54
54
York R-407C Optimized Manual  - Page 55
55
York R-407C Optimized Manual  - Page 56
56
York R-407C Optimized Manual  - Page 57
57
York R-407C Optimized Manual  - Page 58
58
York R-407C Optimized Manual  - Page 59
59
York R-407C Optimized Manual  - Page 60
60
York R-407C Optimized Manual  - Page 61
61
York R-407C Optimized Manual  - Page 62
62
York R-407C Optimized Manual  - Page 63
63
York R-407C Optimized Manual  - Page 64
64
York R-407C Optimized Manual  - Page 65
65
York R-407C Optimized Manual  - Page 66
66
York R-407C Optimized Manual  - Page 67
67
York R-407C Optimized Manual  - Page 68
68
York R-407C Optimized Manual  - Page 69
69
York R-407C Optimized Manual  - Page 70
70
York R-407C Optimized Manual  - Page 71
71
York R-407C Optimized Manual  - Page 72
72
York R-407C Optimized Manual  - Page 73
73
York R-407C Optimized Manual  - Page 74
74
York R-407C Optimized Manual  - Page 75
75
York R-407C Optimized Manual  - Page 76
76
York R-407C Optimized Manual  - Page 77
77
York R-407C Optimized Manual  - Page 78
78
York R-407C Optimized Manual  - Page 79
79
York R-407C Optimized Manual  - Page 80
80
York R-407C Optimized Manual  - Page 81
81
York R-407C Optimized Manual  - Page 82
82
York R-407C Optimized Manual  - Page 83
83
York R-407C Optimized Manual  - Page 84
84
York R-407C Optimized Manual  - Page 85
85
York R-407C Optimized Manual  - Page 86
86
York R-407C Optimized Manual  - Page 87
87
York R-407C Optimized Manual  - Page 88
88
York R-407C Optimized Manual  - Page 89
89
York R-407C Optimized Manual  - Page 90
90
York R-407C Optimized Manual  - Page 91
91
York R-407C Optimized Manual  - Page 92
92
York R-407C Optimized Manual  - Page 93
93
York R-407C Optimized Manual  - Page 94
94
York R-407C Optimized Manual  - Page 95
95
York R-407C Optimized Manual  - Page 96
96
York R-407C Optimized Manual  - Page 97
97
York R-407C Optimized Manual  - Page 98
98
York R-407C Optimized Manual  - Page 99
99
York R-407C Optimized Manual  - Page 100
100
York R-407C Optimized Manual  - Page 101
101
York R-407C Optimized Manual  - Page 102
102
York R-407C Optimized Manual  - Page 103
103
York R-407C Optimized Manual  - Page 104
104
York R-407C Optimized Manual  - Page 105
105
York R-407C Optimized Manual  - Page 106
106
York R-407C Optimized Manual  - Page 107
107
York R-407C Optimized Manual  - Page 108
108
York R-407C Optimized Manual  - Page 109
109
York R-407C Optimized Manual  - Page 110
110
York R-407C Optimized Manual  - Page 111
111
York R-407C Optimized Manual  - Page 112
112
York R-407C Optimized Manual  - Page 113
113
York R-407C Optimized Manual  - Page 114
114
York R-407C Optimized Manual  - Page 115
115
York R-407C Optimized Manual  - Page 116
116
York R-407C Optimized Manual  - Page 117
117
York R-407C Optimized Manual  - Page 118
118
York R-407C Optimized Manual  - Page 119
119
York R-407C Optimized Manual  - Page 120
120
112
YORK INTERNATIONAL
113
YORK INTERNATIONAL
FORM 201.19-EG4
Application Data
APPLICATION DATA:
The YORK YCAS air cooled chillers are designed for
outdoor installation. When selecting a site for installation,
be guided by the following requirements:
1. Installation sites may be either on a roof or ground
level. (See FOUNDATION)
2. Select a place having an adequate supply of fresh air
for the condensers. Recommended clearances for all
units are shown on the DRAWINGS pages.
3. Avoid locations near windows or structures where
normal operating sounds may be objectionable.
4. The standard condenser fans are not recommended
for use with ductwork, lters, or other resistance in
the condenser air stream.
5. When it is desirable to surround the unit, it is rec-
ommended that the screening be able to pass the
required chiller cfm without exceeding 0.1" external
static pressure.
6. Condenser damage from corrosive environments can
be inhibited by providing either copper ns, or cured
epoxy coating on the condenser coils. The cured
phenolic or epoxy coated coils are recommended
for units installed near seashore, or where salt spay
may hit the unit, or where acid rain is prevalent (cop-
per n coils are not recommended where they may
be exposed to acid rain).
7. On installations where winter operation is intended
and snow accumulations expected, additional ele-
vation must be provided to ensure normal condenser
air ow.
FOUNDATION
The unit should be mounted on a at, level foundation,
ground or roof, capable of supporting the entire oper-
ating weight of the equipment as given in the PHYSICAL
DATA tables.
Roof Locations Adequate structural strength to
safely support the entire weight of the unit and service
personnel must be provided. Care must be taken not to
damage the roof during installation. If the roof is “bond-
ed,” consult building contractor or architect for special
installation requirements. Roof installations should in-
corporate the use of isolators to minimize transmission
of vibration into the building structure. Additional support
should be provided to the roof at the isolator locations.
Ground Locations – Units must be installed on a sub-
stantial base that will not settle and cause strain on the
refrigerant lines, which could result in leaks. A one-piece
concrete slab, with footers extending below the frost line
is recommended. The slab should not be connected to
the main building foundation to avoid noise and vibration
transmission.
Mounting holes (0.625" or 16 mm diameter) are provided
in the base rails for bolting the unit to its foundation (See
DIMENSIONS)
For ground installations, take precautions to prevent
tampering by, or injury to, unauthorized persons. Fas-
teners on access panels will prevent casual tamper-
ing, however further safety precautions, such as unit
enclosure options, a fence, or locking devices on the
panels may be advisable. Check local authorities for
safety regulations.
CHILLED LIQUID PIPING
The chilled liquid piping system should be laid out so
the circulating pump discharges into the cooler. The
inlet and outlet cooler liquid connections are given in
DIMENSIONS. Hand stop valves are recommended in
all lines to facilitate servicing. Drain and vent connections
should be provided to permit complete drainage of the
cooler and system piping.
A strainer (40 mesh) is recommended for use on the
INLET line to the cooler, and must be in place upon initial
operation of the water pumps. Anti-vibration couplings
should be considered to inhibit noise and vibration
transmission into the occupied space. Pressure gauge
connections are recommended for installation in the inlet
and outlet water lines. Gauges are not provided with the
units and are by others.
Chilled liquid lines exposed to the weather should be
wrapped with a supplemental heater cable and insu-
lated, or glycol should be added to the chilled liquid
to protect against freezing if low ambient periods are
expected.
A ow switch (available as an accessory) must be in-
stalled in the leaving water piping of the cooler and must
not be used to start and stop the unit.