Figure 7 - Home Screen with Flashing
Service Message
Space Temperature Alarm
Activated when the space temperature is
outside the range of 56-86°F for over 300
seconds. Alarm is available on all
controllers.
Space Humidity Alarm
Activated when the space humidity is above
65% RH for over 300 seconds. Alarm is
only available on controllers with humidity
control.
Fan Fail Alarm
Activated when there is no fan status signal
within 5 seconds on a call for fan. Alarm is
only available on controllers with a fan
status sensor connected.
Low Limit Alarm
Activated when the supply air temperature is
below the low limit alarm temperature
setpoint for 2 seconds (Main Menu:
Advanced: Limits). Cooling will be disabled
until supply air temperature is 2°F above the
low limit setpoint. Alarm is only available
on controllers with a supply air temperature
sensor connected.
High Limit Alarm
Activated when the supply air temperature is
above the high limit alarm temperature
setpoint for 2 seconds (Main Menu:
Advanced: Limits). Heating will be disabled
until supply air temperature is 2°F below the
high limit setpoint. Alarm is only available
on controllers with a supply air temperature
sensor connected.
Space CO
2
Alarm
Activated when the space CO
2
is above
2000 ppm. Alarm is only available on
controllers with CO
2
sensor connected.
Date/Time
Date/Time menu is used to configure the
date and time. Day, month, year and time
are available for configuration.
Schedule
Schedule menu is used to configure an entire
week schedule, a weekday/weekend
schedule or an individual day schedule.
Only one weekly schedule can be setup. Up
to 6 occupied/unoccupied changes can be
made per day. Up to 12 individual days of
unoccupied holidays can be setup within the
menu.
The schedule mode of operation changes
available are On, Off and Null. On is a
change to occupied operation. Off is a
change to unoccupied operation. Null is no
change in mode of operation.
Setpoints
Setpoints menu is used to configure the
controller setpoints.
COOL SETPT
Occupied cooling space temperature
setpoint. Default setpoint is 74°F.
HEAT SETPT
Occupied heating space temperature
setpoint. Default setpoint is 70°F.
COOL SETBACK
Unoccupied cooling space temperature
setpoint. Default setpoint is 80°F.
HEAT SETBACK
Unoccupied heating space temperature
setpoint. Default setpoint is 64°F.