APPLICATION
The gas pressure switch C6097A is used to detect the
pressure of city gas, natural gas,
LP
gas or air etc.
When the gas pressure changes, the diaphragm of the
pressure receiving part detects it and operates the (SPOT)
switch to ON/OFF control of the external electrical circuit.
These switches are widely used to detect the upper limit or
lower limit pressure of gas or air to be supplied to a gas
burner, or to detect the clogging of the interlock filter of a
burner blower.
SPECIFICATIONS
Product
range
There are two versions available: stand alone and flange
mounted, see table 1. and
2.
Table 1. C6097A
flanged
mounted
models
Model
Operating
Nominal
Maximum
pressure
operating
working
range
differential
pressure
(mbar) (mbar) (mbar)
C6097A2200 2.5
...
50 0.6
300
C6097A2300 30
...
150 2.8
500
C6097A2400 100
...
500 7.0
600
Honeywell
UNIVERSAL GAS VALVES
C6097A
GAS
PRESSURE
SWITCHES
INSTRUCTION
SHEET
Table 2. C6097A
stand
alone
models
Model
Operating
Nominal
Maximum
pressure
operating
working
range
differential
pressure
(mbar)
(mbar) (mbar)
C6097A2110 1.0
...
10 0.4 200
C6097A2210 2.5
...
50 0.6
300
C6097A2310 30
...
150 2.8
500
C6097A2410 100
...
500 7.0
600
NOTE: The operating differential
IS the difference between
the upper and lower operating pressures at one set
point.
Dimensions
See Figure 1.
Connection
Inlet positive pressure Rp1/4" internal pipe thread (2
x).
Differential pressure
Rp
1/8" internal pipe thread.
All connections according to ISO 7-1
Set
point
accuracy
15% of the full scale (when pressure is increased)
NOTE: The knob readings are approximations of the actual
settings.
Torsion
and
bending
stress
Pipe connections meet group
2,
according to EN161
requirements.
Contact
ratings
Resistive load: 250 Vac, 5A
Inductive load: 250 Vac, 3A (power factor 0.6)
Minimum contact current and voltage: 50 mA, 24 Vac
Material
of
pressure
receiving
parts
NBR single diaphragm
Material
of
housing
Aluminium
die-cast
Material
of
case
Polybutylene terephthalate
Material
of
cover
Polycarbonate
Ambient
temperature
range
-15
...
60 C
Relative humidity: max. 90% at 40 C (non-condensing)
Sensed
medium
temperature
range
-15
...
80 C
Electrical
connection
Plug connection according to
PG11
or three pin plug
connector ("DIN plug")
Protection against electrical shock: class I
Wire
connection
terminals
M3.5 screw terminals, including earth connection
EN1
R-9172
9907R1-NE