less than 30 seconds eliminates the requirement for a system reboot. Hot-swapping a fan in less
than two minutes enables continued operation and prevents automatic shutdown.
CAUTION: Operating the server with the front grill removed risks EMI. Operate the server
with the front grill removed only when hot-swapping a fan. Always replace the front grill
immediately after replacing a fan.
Observe all ESD safety precautions while performing this procedure. Failure to follow ESD safety
precautions can result in damage to the server.
NOTE: A hot-swap device does not require interaction with the operating system before the
device is removed from or installed into the server.
The power to the server does not have to be off to remove or replace a hot-swappable chassis
fan unit.
Removing and Installing a Front Panel Hot-Swap Fan
Figure 3-7 Removing a Front Panel Hot-Swappable Fan
The server does not need to be removed or extended from the rack to enable fan replacement.
Installing Hot-Swap Chassis Fan Units 31