Haier 0010516146 Installation Manual

Download Installation manual of Haier 0010516146 Air Conditioner for Free or View it Online on All-Guides.com. This version of Haier 0010516146 Manual compatible with such list of devices, as: 0010516146, 10516146, HSU-07HEA03/R2, HSU-09HEA103/R2, HSU-22HEA03/R2

Haier 0010516146 Installation manual - Page 1
1
Haier 0010516146 Installation manual - Page 2
2
Haier 0010516146 Installation manual - Page 3
3
Haier 0010516146 Installation manual - Page 4
4
Haier 0010516146 Installation manual - Page 5
5
Haier 0010516146 Installation manual - Page 6
6
Haier 0010516146 Installation manual - Page 7
7
Haier 0010516146 Installation manual - Page 8
8
Haier 0010516146 Installation manual - Page 9
9
Haier 0010516146 Installation manual - Page 10
10
Haier 0010516146 Installation manual - Page 11
11
Haier 0010516146 Installation manual - Page 12
12
Haier 0010516146 Installation manual - Page 13
13
Haier 0010516146 Installation manual - Page 14
14
Haier 0010516146 Installation manual - Page 15
15
Haier 0010516146 Installation manual - Page 16
16
Haier 0010516146 Installation manual - Page 17
17
Haier 0010516146 Installation manual - Page 18
18
Haier 0010516146 Installation manual - Page 19
19
Haier 0010516146 Installation manual - Page 20
20
Haier 0010516146 Installation manual - Page 21
21
Haier 0010516146 Installation manual - Page 22
22
Haier 0010516146 Installation manual - Page 23
23
Haier 0010516146 Installation manual - Page 24
24
Haier 0010516146 Installation manual - Page 25
25
Haier 0010516146 Installation manual - Page 26
26
Haier 0010516146 Installation manual - Page 27
27
Haier 0010516146 Installation manual - Page 28
28
Haier 0010516146 Installation manual - Page 29
29
Haier 0010516146 Installation manual - Page 30
30
Haier 0010516146 Installation manual - Page 31
31
Haier 0010516146 Installation manual - Page 32
32
Haier 0010516146 Installation manual - Page 33
33
Haier 0010516146 Installation manual - Page 34
34
Haier 0010516146 Installation manual - Page 35
35
Haier 0010516146 Installation manual - Page 36
36
Outdoor unit
5.Purging Method:To use vacuum pump
Detach the service port's cap of 3-way valve, the
valve rod's cap for 2-way valve and 3-way's, connect
the service port into the projection of charge hose
(low) for gaugemanifold. Then connect the projection
of charge hose (center) for gaugemanifold into
vacuum pump.
Tube(for R410A)
Open the handle at low in gaugemanifold, operate
vacuum pump. If the scale-moves of gause (low)
reach vacuum condition in a moment, check again.
Vacuumize for over 15min. And check the level gauge
which should read -0.1 MPa (-76 cm Hg) at low
pressure side. After the completion of vacuumizing,
close the handle 'Lo' in gaugemanifold and stop the
operation of the vacuum pump.
Check the condition of the scale and hold it for 1-2min.
If the scale-moves back in spite of tightening, make
flaring work again, the return to the beginning of .
Open the valve rod for the 2-way valve to an angle of
anticlockwise 90 degrees.
After 6 seconds, close the 2-way valve and make
the inspection of gas leakage.
No gas leakage?
In case of gas leakage, tighten
parts of pipe connection. If
leakage stops, then proceed
steps.
Detach the charge hose from the service port, open
2-way valve and 3-way. Turn the valve rod anticlockwise
until hitting lightly.
To prevent the gas leakage, turn the service port's
cap, the valve rod's cap for 2-way valve and 3-way's
a little more than the point where the torque increases
suddenly.
After attaching the each caps, check the gas leakage
around the caps.
CAUTION:
1.If the refrigerant of the air conditioner leaks, it is necessary to
discharge all the refrigerant. Vacuumize first, then charge the liquid
refrigerant into air conditioner according to the amount marked on
the name plate.
2.Please do not let other cooling medium, except specified one (R410A),
or air enter into the cooling circulation system. Otherwise, there will be
abnormal high pressure in the system to make it crack and lead to
personal injuries.
If it does not stop gas leakage, discharge
whole refrigerants from the service port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder
3-way valve
Gas Side
9.52mm(3/8")
6.35mm(1/4")
2-way valve
3-way valve
Service port cap
Gaugemanifold(for R410A)
Anti countercurrent joint
Vacuum pump(for R410A)
Open
Close
Liquid Side
2-way valve
Valve rod cap
Valve rod cap
2-way valve
9.52mm(3/8")
6.35mm(1/4")
3-way valve
12.7mm(1/2")
Gas Side
Liquid Side
2-way valve
3-way valve
3-way valve
2-way valve
Service port
90
o
Open
90
o
for 6 sec.
12.7mm(1/2")
HSU-07HEA03/R2
HSU-09HEA03/R2
HSU-09HEA103/R2
HSU-12HEA03/R2
HSU-18HEA03/R2
3-way valve
2-way valve
6.35mm(1/4")
12.7mm(1/2")
90
Gas Side
Liquid Side
HSU-22HEA03/R2
6