Federal law requires that WINEMATE split cooling systems be
installed by an EPA certified refrigeration technician.
1. Location
Place the condensing unit in a properly ventilated location. If it is not, heat
exhausted by the condensing unit will build up and the cooling system will
not operate properly.
Leave minimum 3 feet clearance between the exhaust side and the wall.
Leave minimum 1 foot clearance for the fresh air supply side.
Condensing unit should be elevated to avoid possible flooding and shaded
from direct sun. It should not be exposed to temperatures higher than 125
°F or lower than 20 °F.
Air flow from the unit cooler should be unobstructed for at least 1 foot.
2. Refrigeration Installation
Model Liquid Line Diameter
(inch), recommended
Suction Line Diameter
(inch), recommended
VINO1500SS 1/4 3/8
VINO1900SS 1/4 3/8
WINEMATE split system is shipped as components and is ready for use only
after a certified refrigeration technician has properly installed and tested the
system. Proper installation is critical. WINEMATE can only warrant the quality of