- 1 -
Step-by-Step
Tech Support
Updated 11/2/07
- Single 4-Wire Smoke Zone with Sounders -
Objective Equipment List
To activate the sounders on
all smokes after any smoke
detector is activated
Apex Destiny 6100 Control Panel, rev. 8.05 or greater
System Sensor Smokes: 4WTA-B, 4WTAR-B, 4WITAR-B
System Sensor RRS-MOD
Sequence of Operation
When the panel detects an alarm from any fire zone, the panel will activate the on board relay to activate the trigger
wire (purple see wiring diagram below) which in turn with sound ALL sounders.
To Reset:
1. Press Code 1 time
2. Press Code + 6 (Smoke Power Reset)
3. Arm and Disarm the panel (to Clear the Alarm Memory)
Required Programming
Location Value Function
9940 01 (zone #) Zone Type = 006
Zone Options 1 = 080
Zone Options 2 = 001
Device Type = 000 (onboard zones) or 001 (Zone Expander HWB416)
Enter the 2 digit input # (001 in this case)
4097 001 Enable Control Channel 1
4119 008 Assign Control Channel 1 to the on-board relay
0185 001 Assign the “fire” Trigger
4055 006 002 (on – on any fire alarm) + 004 (off – restore action for fire alarm is
disarming the control) = 006
See Below for the wiring Diagram: