Honeywell Gent Vigilon A3 Mimic Data And Installation

Download Data and installation of Honeywell Gent Vigilon A3 Mimic Touch Panel for Free or View it Online on All-Guides.com.

Honeywell Gent Vigilon A3 Mimic Data and installation - Page 1
1
Honeywell Gent Vigilon A3 Mimic Data and installation - Page 2
2
Honeywell Gent Vigilon A3 Mimic Data and installation - Page 3
3
Honeywell Gent Vigilon A3 Mimic Data and installation - Page 4
4
Customised Mimic
Zonal Mimic
A Vigilon A3 Mimic panel (VIG-MIM-A3) must be
connected to a loop circuit of a Vigilon fire detection and
alarm system. It is used to provide indication of fire
events in the system. However it can also be used to
provide indication of fault and supervisory events in the
system. The panel can be mounted in landscape or
portrait orientation.
A Customised Mimic holds a pictorial overlay that
represents the protected building or an area within. A fire
event is indicated by the illumination of appropriate red
LEDs behind the overlay to show the location of the fire.
A Zonal Mimic provides a traditional zone by zone
indication of a fire. Each zone is given a location label to
identify the area within a building.
The panel illumination defaults to a Zonal Mimic but can
be reprogrammed during commissioning to be a
Customised Mimic. An array of red lights illuminates
individually or in groups. Illuminations may be applied to
include custom shapes, text and digital clock in small or
large size. A site specific 'welcome message' may be
configured for display during quiescent conditions that
can scroll if it is too long to fit the display area. First or
last fire flashing option, with in phase or anti phase flash.
The panel has its own mains derived power supply with
battery for standby power in the event of mains supply
failure.
Technical Data
Panel dimensions height 403mm, width 338mm,
depth 101mm
Weight 7.9Kg without batteries
10.5Kg with batteries
Storage temperature -10 to 55ºC
Operating temperature 0 to 45ºC
Relative humidity
(Non condensing)
Up to 90% temperature
5-45°C
Battery 2 x 6V 7Ah sealed lead acid
(weight 1.3Kg each)
The integral battery provides
power for 72 hours in standby
condition and a further
30 minutes in alarm.
Mains operating
voltage
230V 50Hz +10% -6%
Emission BS EN61000-6-3 : 2001
Immunity BS EN50130-4 : 1996 : Part 4
LVD BS EN 60950-2006
Ingress protection IP30 (estimated)
Colour
Door - Pantone 422
Back box - Graphite Grey
(RAL 7024)
Control Cancel fault buzzer / lamp test
button
Indicators 1536 high intensity RED LEDs.
Loop connection 3-way connection to a loop
circuit
Maximum number per
loop
(A maximum load
factor of 1000 allowed
per Vigilon loop circuit)
Maximum number of combined
repeat and mimic panels per
loop = 4
load factor per panel = 3
Typical Mimic illuminations
4188-945_issue 2_05/10_pt1_A3 Mimic 1
Data and Installation
Vigilon A3 Mimic panel
VIG-MIM-A3
by Honeywell
Flashing in phase
or anti phase
Customised Mimic Zonal Mimic
ZONE n
Zone in fire
- steady indication
Latest zone in fire
- flashing indication