GENERAL
Below are descriptions of option packages available on the
Sunline Plus (3 and 7.5 through 20 ton) and Sunline Ultra (3,4
and 5 ton) units. There are 4 option packages, the: BASE OP-
TION PACKAGE, PROTECTION PACKAGE, INSTALLATION
PACKAGE, and CABINET PACKAGE. The BASE OPTION
PACKAGE can be ordered alone, but is always included with
any of the other option packages.
FACTORY OPTIONS
The following factory options can be ordered in conjunction
with any of the OPTION PACKAGES:
A. No Economizer.
B. Dry Bulb Economizer.
C. Dry Bulb Economizer with Power Exhaust (15 & 20 ton unitsonly).
NOTE:Not all combinations of base units and option packages
are available. See the Price Pages for specific model
and option combinations.
All option packages are available with the dry bulb
economizer option only.
Individual items within each package can not be
broken-out and ordered separately.
BASE OPTION PACKAGE
A. High-speed drive (15 & 20 ton units) includes a belt and
blower pulley upgrade, an alternate hp motor (7 - 12 tons)
or the belt drive option (3 - 5 tons).
B. Self-priming condensate cover
assistsinprimingadrytrap.
C. A sloped drain pan
to prevent standing water in the drain
pan.
NOTE:The internal drain connection is not offered with the
sloped drain pan design on the 15 & 20 ton units.
D. Smoke detector terminal block provisions
provide field-
wiring means for powering a 24VAC duct smoke detector
and a single set of normally closed contacts, which open to
shut down the unit upon detection of smoke. Although the
air conditioning unit is shut down when the smoke detector
alarms, the 24V power supply to the smoke detector is not
interrupted. Actual mounting means for the smoke detector
are not provided due to the wide variation in regulations
and codes.
CAUTION: Normal maintenance activity will require discon-
necting power to the unit. When the YORK sup-
plied terminal strip is used to provide 24V power to
a smoke detector; the smoke detector will not be
powered when the power supply is interrupted to
the unit. If the smoke detector is linked to separate
monitoring system that would detect this power
shutdown and report it as an alarm condition, do
not use the unit terminal strip to power the smoke
detector.
24 VAC
POW ER SUPPLY
5VA (M ax.)
NORMALY
CLO SED
CONTACTS
24 VAC
UNIT W IRING
UNIT W IRING
TERM INAL
BLO CKS
(located in
Econom izer
section)
Field S upplied W iring
Wired to
24 VAC
pow er
te rm in a ls
of sm oke
d e te c to r
JUM PER
Remove
ju m p e r a n d
w ire to th e
norm ally
closed
contacts of
th e s m o k e
detector
SMOKE DETECTOR TERMINAL BLOCK DIAGRAM
®
OPTION PACKAGES
INSTALLATION INSTRUCTION
Supersedes: 530.24-N1Y (199)
035-16134-000 Rev. A (0501)
FOR SUNLINE
MODELS DHE, DHG 036, 048 & 060, 180 & 240
MODELS DEE, DEG 036