<E1. Standard Specication>
E1-1
IM 01W02D02-01EN
Part-E. Specications
E1. Standard Specication
n Communication interface
ITEM
Field Wireless Backbone
Specications
Optical Network Specica-
tions
Communication Inter-
face
Standard 100BASE-TX
*1
100BASE-FX
*2
Transmission Speed 100Mbps 100Mbps
Connector RJ-45 SC connector [1pole x 2]
Cable Type Category 5
Multi-Mode Fiber
50/125 or 62.5/125μm (2
cores)
Center Wavelength – 1300nm
Maximum Length 100m 2000m
Number of Ports 4 ports 4 ports
Port Name B1, B2, B3, B4 1, 2, 3, 4
Protection Surge –
Port Connection B1-1, B2-2, B3-3, B4-4 (xed)
*1: Connect to YFGW410
*2: Connect to YFGW510. In outdoor wiring, use optical ber cables with a nonmetallic tension member.
n Installation Environment
Temperature Range:
Operating: -40 to +65°C (altitude : up to 2000m)
-40 to +55°C (altitude : more than
2000m, up to 3000m)
Storage: -40 to +85°C
Humidity Range:
Operating: 5 to 95 %RH (non-condensation)
Storage: 5 to 95 %RH (non-condensation)
Temperature gradient:
Operating: ±10°C/h or less
Storage: ±20°C/h or less
Power Supply:
Voltage Range : 10.8~26.4 V DC
Rated Power Supply : 24 V DC
Momentary Power Failure : Instant Disconnection
DC Power Supply Ripple Ratio : 1%p-p or less
Power Consumption:
Max. 10 W
Degrees of Protection:
IP20
Vibration resistance:
0.15 mm P-P (5~58 Hz), 1 G (58~150 Hz)
Shock resistance:
15 G 11 ms
Noise resistance:
Electric eld : 3 V/m or less (80MHz~1GHz)
Electrostatic discharges: 4 kV or less (contact
discharge), 8 kV or less (aerial discharge)
Grounding:
Class-D grounding (no sharing ground with
others)
Cooling:
Natural Air Cooling
n Regulatory Compliance State-
ments
EMC Conformity Standards:
EN61326-1 Class A, Table 2 (for industrial use),
EN55011 Class A group1, EN61000-6-2
Safety Requirements:
EN61010-1, CSA C22.2 No. 61010-1
Indoor use only
Explosion-Proof Types:
FM, ATEX, CSA, IECEx (approvals under
pending)
n Physical Specications
Housing Material:
Aluminum alloy plate with polyester, mint-green
paint
(Munsell 5.6BG 3.3/2.9 or its equivalent)
External Dimension:
150 x 60 x 140 mm (not include projection)
Weight:
Approx. 1.0 kg
Mounting:
DIN RAIL Mounting