Bosch MAGIC.SENS MSS 400 Installation Details

Download Installation details of Bosch MAGIC.SENS MSS 400 Marine Equipment for Free or View it Online on All-Guides.com.

Bosch MAGIC.SENS MSS 400 Installation details - Page 1
1
Bosch MAGIC.SENS MSS 400 Installation details - Page 2
2
Page 1
BDL - 4998121822
A4.en/ 23.08.2007
ST-FIR/ PRM1/ deh
INSTALLATION DETAILS MAGIC.SENS MSS 400
Fixing notes
The sounder base is designed for surface mounting and is provided for rear and surface cable
entry. The sounder insert has to be removed before fixing the mounting base. To release the
sounder insert, fixing clamps have to be pushed in direction of the arrows (Fig.2). for rear
cable entry, conduit box mounting, feed the cable through the openings. For surface cable
feed, please break out the prepared cable entries. Install the mounting base with two screws
on a flat dry surface. Therefore, only the prepared fixing bores may be used (see Fig. 2)!
Technical Data
Dimensions : see Figure 1 and Figure 2
IP-Rating (as per EN 60529): IP30
Operating temperature: -10_C...+55_C
Storage temp erature: -25_C...+85_C
Housing material: ABS plastics
Terminals: In and Out 0,28 - 2,5mm
2
Operating voltage: 9 - 15V DC / 15 - 28V DC
Current consumpt. from LSN (standby): 575 - 1025mA
Current consumption from LSN (alarm): 20mA
(depending on selected tone)
Bosch order number: 4.998.098.974
CPD number: 0786 - CPD - 20186
128
81,5
Sounder insert
Mountin g ba se
Detector
Fixing springs
Fi gu re 1: Dimens i o ns Fi gu re 2: Instal l ati o n de tai ls
Fi gu re 3: Mounting ord er
Figure 4: Detector lo cking spring
Detector with sounder
base (complete f itted)
70
60
50
Cable entries for
under plaster cable feed
Use only these borings for
fixing the mounting base!
Sounder insert
fixing clamps
to
release
sounder
insert
Prepared cable
entries
Prepared cable
entries
Tone table