Alfa Laval ThinkTop Installation instruction - Page 1
1
Alfa Laval ThinkTop Installation instruction - Page 2
2
1.
2.
3. 4. 5.
Installation on air
actuators:
1. Remove the cover by loosening the
four cross recess screws.
2. Separate the adapter from the base
by loosening the three recess screws
on top of the base.
1. Fit air fittings on actuator.
2. Position packing retainer in recess on
actuator top.
3. Fit counter nut and indicator (magnet)
on actuator rod. Engage approx. ¼”
thread. Tighten counter nut and
indicator with two wrenches.
1. Place the two O-rings in the grooves in the
bottom of the adapter. Then place the adapter
on the actuator top. The small O-ring must be
positioned over the air hole on the actuator.
2. Fasten the adapter with the four 5/16” Allen
screws.
Mount the base on the adapter in the
position needed (can be rotated 120°
in both directions). Note that one of the
screw towers on the adapter has a guide
recess (see on drawing).
Fit ¼” air hose to ThinkTop and actuator
(see drawing “Air Connections” (point 8
next page)).
TD 800-170
TD 800-250
TD 800-170
IM70851EN3 2009-03
ThinkTop
®
for series 700 valves Digital 8-30 VDC PNP/NPN
Installation Instruction
9611-99-4175
Alfa Laval Kolding A/S, www.alfalaval.com
TD 800-251